Regenerative 4-Quadrant AC Load – Model 9430
Regenerative AC Load with Linear & Non-Linear AC Loading in Several Emulation Modes with User-Defined Waveforms, Power & Crest Factor Control.
Features
Model 9430 Regenerative AC Load Specifications
Model # |
9430-4 |
9430-8 |
9430-12 |
9430-24 |
9430-36 |
9430-48 |
9430-72 |
9430-96 |
AC Loading Programmability |
||||||||
Phases/Output Channels |
Single |
Single, Split-Phase |
Single, Split or 3-Phase |
|||||
Input Voltage (LR,HR) |
10-175, 350VRMS L-N (split-phase limited to 250V max) |
|||||||
Current Limit Set Ranges (per ф) |
0-6, 30A (1ф) |
0-6, 30A (1ф) |
0-6, 30A (3ф) |
0-12, 60A (3ф) |
0-18, 90A (3ф) |
0-24, 120A (3ф) |
0-36, 180A (3ф) |
0-48, 240A (3ф) |
Current Limit Set Max (per load) |
0-6, 30A (1ф) |
0-12, 60A |
0-18, 90A |
0-36, 180A |
0-54, 270A |
0-72, 360A |
0-108, 540A |
0-144, 720A |
Power Limit Set Max (1, Split, 3ф) |
4kW |
8, 8kW |
12, 8, 12kW |
24, 16, 24kW |
36, 24, 36kW |
48, 36, 48kW |
72, 48, 72kW |
96, 64, 96kW |
Maximum Reactive Power |
10.5kVA |
21kVA |
31.5kVA |
63kVA |
94.5kVA |
126kVA |
189kVA |
252kVA |
DC Loading Programmability |
||||||||
Input Voltage |
10-400VDC |
|||||||
DC Loading Modes |
Constant Voltage (CV), Constant Current (CC), Constant Power (CP), Constant Resistance (CR) in any combination |
|||||||
Current Limit Set Ranges |
0-6, 30A |
0-12, 60A |
0-18, 90A |
0-36, 180A |
0-54, 270A |
0-72, 360A |
0-108, 540A |
0-144, 720A |
Power Limit Set Max |
0-4kW |
0-8kW |
0-12kW |
0-24kW |
0-36kW |
0-48kW |
0-72kW |
0-96kW |
Physical |
||||||||
Enclosure |
Chassis |
Chassis |
Chassis |
Cabinet |
Cabinet |
Cabinet |
Cabinet (double) |
Cabinet (double) |
Size (HxWxD) |
10 1/2 x 19 x 28″/ |
15 3/4 x 19 x 24″/ |
15 3/4 x 19 x 24″/ |
49 x 23 x 30″/ |
61 x 23 x 30″/ |
78 x 23 x 30″/ |
78 x 46 x 30″/ |
78 x 46 x 30″/ |
Weight |
150lbs/ |
150lbs/ |
155lbs/ |
480lbs/ |
640lbs/ |
780lbs/ |
1280lbs/ |
1560lbs/ |
* The above specifications show typical configurations & subject to change. Contact NH Research, Inc. for further information. |
Advantages
Multiple Loading Modes including:
Built in measurement system:
Software tools to shorten test development time:
Benefits
Applications
The 9430 is a current-regulated, 4-quadrant AC load with selectable phase inputs/outputs and a built-in waveform digitizing measurement system. In the sink mode, it sends power back to the facility mains rather than dissipated as heat. The 9430 has the capability of simulating almost any linear or non-linear load. Applications include testing of UPSs, AC sources, inverters, rectifiers, switches, circuit breakers and fuses.